Size: 1.3125 Inch x 7.875 Inch
Detailed Description:
Ferraz Shawmut Tri-OniC® TRS Series Class RK5 Time delay fuse is rated at 70 Amps/600 VAC/600 VDC. It has an interrupt rating of 200 kilo-Amps AC and 20 kilo-Amps DC. Fuse comes in fiberglass body construction offers dimensional stability in harsh industrial settings. It has high-grade silica filler that ensures fast arc quenching and high current limitation. It features time delay for motor start-ups and transformer inrush currents without nuisance opening. It measures 1.3125 Inch x 7.875 Inch.
Fuse has optional solid-state SmartSpot indicator and features rejection-style design that prevents replacement errors. It comes with easy-to-read label for quick recognition and replacement. It is designed for motor circuits, mains, feeders, branch circuits, transformers, service entrance equipment and general-purpose equipment. Fuse is UL listed and CE/CSA certified.
Amperage Rating | 70 |
Application | Motor circuits Mains Feeders Branch circuits Transformers Service entrance equipment General-purpose equipment |
Brand | Mersen |
Catalog Description | Tri-Onic TRS-R current-limiting time-delay fuses are engineered for overcurrent protection of motors, transformers, service entrance equipment, feeders and branch-circuits. The time-delay characteristics of the TRS-R safely handle harmless starting currents and inrush currents associated with todayÆs motors and transformers. 600 Volts 70 amps TRS series. |
Connection | Blade |
GTIN |
00782001749071 |
Height | 1.3130 |
Height Unit | IN |
Interrupt Rating | 200 |
Item Status | A |
Length | 7.8750 |
Length UOM | IN |
Mfr. # | TRS70R |
Mounting | Clip |
Size | 7.88 x 1.31 |
Special Features | Time-delay Current-limiting AC & DC rated Optional solid state SmartSpot blown fuse indicator Time-delay for motor start-ups and transformer inrush currents without nuisance opening Current-limiting for low peak let-thru current Rejection-style design prevents replacement errors (when used with recommended fuse blocks) Easy-to-read label for quick brand recognition and replacement Metal-embossed date and catalog number for traceability and lasting identification Fiberglass body provides dimensional stability in harsh industrial settings High-grade silica filler ensures fast arc quenching and high current limitation |
Standard | UL listed to standard 248-12 File E2137 CSA certified to standard C22.2 no. 248.12 DC listed to UL standard 248 TRS only |
Sub-Brand | Tri-Onic |
Type | Class RK5 |
UNSPSC | 39121606 |
Voltage Rating | 600 |
Width | 1.3130 |
Width UOM | IN |