Size: 1.3125 Inch x 7.875 Inch
Metal embossed date and catalog number for easier traceability and lasting identification
Detailed Description:
Ferraz Shawmut Amp-Trap 2000® Class RK1 Time delay fuse operates at a current rating of 80 Amps and voltage rating of 600 VAC/600VDC. It has an interrupt rating of 200 kilo-Amps AC and 100 kilo-Amps DC. Fuse comes in fiberglass body construction offers dimensional stability in harsh industrial settings and has solid state SmartSpot indicator. It features time delay for motor start-ups and transformer inrush currents without nuisance opening. It measures 1.3125 Inch x 7.875 Inch.
Fuse features rejection-style design that prevents replacement errors. It has high-visibility orange label that gives instant recognition quick recognition. It is designed for motor circuits, mains, feeders, branch circuits, transformers, service entrance equipment and general-purpose equipment. Fuse is UL listed and CE/CSA certified.
Amperage Rating | 80 |
Application | Motors Safety switches Transformers Branch circuit protection Disconnects Control panels All general-purpose circuits |
Brand | Mersen |
Catalog Description | Amp-Trap 2000 SmartSpot time-delay A6D-R fuses provide IEC Type 2 "no damage" protection to existing mains, feeders, and branch circuits serving motor and non-motor loads. A6D-R fuses will open fast enough under extreme fault conditions for maximum short circuit protection to prevent damage to motor starters, switches, and other circuit components, yet also provide the time-delay needed for motor in-rush currents. A6D-R fuses can be used to replace 600V Class H, K or RK5 fuses already installed in the field. 600 Volts 80 amps. |
Connection | Blade |
GTIN |
00782001992095 |
Height | 1.3100 |
Height Unit | IN |
Interrupt Rating | 200 |
Item Status | A |
Length | 7.8750 |
Length UOM | IN |
Mfr. # | A6D80R |
Mounting | Clip |
Size | 7.88 x 1.31 |
Special Features | Non-indicating or Solid state SmartSpot visual blown fuse indicator Time-delay for motor starting and transformer inrush currents without nuisance opening 600VAC & 600VDC dual rated 300kA interrupting rating - self-certified, UL witnessed tests Extremely current-limiting for low peak let-thru current Recommended for Arc Flash energy reduction Easy 2-to-1 selectivity for prevention of nuisance shut downs and black outs Rejection-style design prevents replacement errors (when used with recommended fuse blocks) High-visibility orange label gives instant brand recognition Reduced inventory by taking the place of class RK5, K, and H fuses Metal-embossed date and catalog number for easier traceability and lasting identification Fiberglass body provides dimensional stability in harsh industrial settings |
Standard | UL listed to standard 248-12 File E2137 DC listed to UL standard 248 CSA certified to standard C22.2 No. 248.12 |
Sub-Brand | Amp-Trap 2000 |
Type | Class RK1 |
Type Of Indicators | SmartSpot |
UNSPSC | 39121606 |
Voltage Rating | 600 |
Width | 1.3100 |