Sign in or register to view your pricing and inventory.

Eaton / Cutler Hammer V48M22T30EE Dry Type Transformer; 480 Volt Primary, 240 Volt Secondary, 30 KVA, 3 Phase

  • Eaton / Cutler Hammer V48M22T30EE Eaton / Cutler Hammer V48M22T30EE Dry Type Transformer; 480 Volt Primary, 240 Volt Secondary, 30 KVA, 3 Phase
  • Eaton / Cutler Hammer V48M22T30EE Dry Type Transformer; 480 Volt Primary, 240 Volt Secondary, 30 KVA, 3 Phase
Manufacturer: Eaton / Cutler Hammer
Mfr. #: V48M22T30EE
Item #: 108337
UPC: 786680029707
Login for Availability
Your Price:

Product Details

Dimension: 16.500 Inch Length x 23 Inch Width x 30 Inch Height

912B frame

WS38 weather shield

With 120 Volt lighting tap on Phase B

Detailed Description: Eaton 3-Phase Dry type transformer comes with a ventilated enclosure and has a voltage rating of 30 kVA. It measures 16.500 Inch x 23 Inch x 30 Inch. Step-down transformer has a secondary voltage rating of delta 240 Volts and a primary voltage rating of 480 Volts delta at 60 Hz frequency. Ventilated design enclosure is perfect for indoor environment. It has 2.5% taps with two taps above FCAN and four below FCBN to compensate higher non-linear load loss.

Transformer has high quality aluminum wire winding to provide effective operation. Insulation wire has 220 deg C system standards to resist high temperature for securing the coil. It has a temperature rise of 150 deg C due to heat generated in the internal structure. Transformer is UL listed.

Product Specification

Application Commercial / Institutional Buildings / Structures - Power Distribution and Controls
Brand Eaton
Catalog Description Eaton General purpose ventilated transformer, DT-3 (3-phase), PV 480V, Taps: 2 at +2.5% /4 at -2.5%, SV 240 delta/120 midtap, 150¦C rise w/ 200¦C insulation systeam, 30 kVA, EE
Frequency Rating 60
GTIN

00786680029707

Height 30.0000
Height Unit IN
Item Status A
Length 16.5000
Length UOM IN
Mfr. # V48M22T30EE
Number Of Phases Three-phase
Primary Voltage 480
Secondary Voltage 240 delta/120 midtap
Standard UL Listed,NEMA TP-1 Compliant
Tap Size 2 at +2.5% FCAN, 4 at -2.5% FCBN
Temperature Rating 150 C rise
Type Ventilated transformer
UNSPSC 39121029
Width 23.0000
Width UOM IN